Structural Design And Analysis For Concrete Building - Building complex

 

Structural Design Criteria 

1. Codes and Standards

Unless otherwise specified herein, the following tables list the codes and manuals that shall be followed in design.

LOADS

BS 6399 - 1: 1996

Loading for buildings - Part 1. Code of Practice for Dead and Imposed Loads

BS 6399 - 2: 1997

Loading for buildings - Part 2: Code of practice for wind loads

BS 6399 - 3: 1988

Loading for buildings - Part 3: Code of Practice for Imposed Roof Loads

 

 

reinforced concrete

QCS 2010

Qatar Construction Specifications

BS 8110 - 1: 1997

Structural use of concrete Part 1: Code of Practice for Design and Construction

BS 8110 - 2: 1985

Structural use of concrete Part 2: Code of Practice for Special Circumstances

BS 8110 - 3: 1985

Structural use of concrete Part 3: Design Charts for Singly Reinforced Beams, Doubly Reinforced Beams and Rectangular Columns

BS 8004: 1986

Code of Practice for Foundations


construction-buildings-concrete-structural-analysis-design-structural design of building,concrete building design,design of concrete structure,building design in prota structure,design of concrete structures,building structures,deterioration of concrete structures,design of concrete structure lectures,design of reinforced concrete structures

construction-buildings-concrete-structural-analysis-design-structural design of building,concrete building design,design of concrete structure,building design in prota structure,design of concrete structures,building structures,deterioration of concrete structures,design of concrete structure lectures,design of reinforced concrete structures
construction-buildings-concrete-structural-analysis-design-structural design of building,concrete building design,design of concrete structure,building design in prota structure,design of concrete structures,building structures,deterioration of concrete structures,design of concrete structure lectures,design of reinforced concrete structures
construction-buildings-concrete-structural-analysis-design-structural design of building,concrete building design,design of concrete structure,building design in prota structure,design of concrete structures,building structures,deterioration of concrete structures,design of concrete structure lectures,design of reinforced concrete structures

construction-buildings-concrete-structural-analysis-design-structural design of building,concrete building design,design of concrete structure,building design in prota structure,design of concrete structures,building structures,deterioration of concrete structures,design of concrete structure lectures,design of reinforced concrete structures





2. Material Requirements

2.1 Concrete Grades

The characteristic concrete cube compressive strength after 28 days in N/mm2 shall be as follows:

Cast-in-situ reinforced concrete                                                                            35  MPa

Cast-in-situ reinforced concrete for slab-on-grade                                                                   30  MPa

Blinding concrete                                                                                                       20  MPa

 

2.2  Reinforcing Rebar

Uncoated mild steel plain bars according to BS 4449 denoted “R"

Minimum yield Stress                                                                                    250  N/mm2


High tensile steel deformed bars according to BS 4449 denoted “T"

Minimum yield Stress                                                                                    460  N/mm2

Steel wire fabric mesh according to BS 4483

Minimum yield Stress                                                                                                   460  N/mm


2.3 Concrete Cover 

The cover shall not be less than as given below, according to the type of structural member and the placing and exposure conditions as follows:

·   Condition 1: Concrete placed in forms and not to be exposed later to the weather, groundwater, freshwater, or to any combination of these.               

·   Condition 2: Concrete placed in forms but later to be exposed to the weather, groundwater, freshwater, or to any combination of these.

·   Condition 3: Concrete placed directly in contact with the ground.

·   Condition 4: Concrete to be exposed to corrosive vapors, corrosive groundwater, seawater or sea spray. Sufficient protection to the reinforcement shall be provided by: adopting the minimum cover for exposure condition 3 and applying a protective coating or membrane on the concrete surface. The method of protection shall be in accordance with the provisions of the specification and to the approval of the Engineer.

 

Structural Member

Minimum Cover (mm) for Placing of Reinforcement for Exposure Condition

Condition 1

Condition 2

Condition 3

Pad footings and Pile Caps

-

65

75

Strip footings

-

50

65

Bored or Cast Piles

-

50

75

Columns of all types

30

40

75

Walls, including retaining walls

25

30

75

Beams

30

40

65

Slabs, including concrete joist and

hollow block construction

25

30

65

Cover to embedded pipes

25

30

65

Reinforcement adjacent to blocks in

hollow block slab construction which

are integral with the structure

10

-

-

 

3. Loading


3.1      Dead Loads

3.1.1   Unit Weight of Materials

Unit weight of reinforced concrete                                                                 24.0 kN/m3

Unit weight of plain concrete                                                                          22.0 kN/m3

Unit weight of block walls 20 cm*20cm*40cm (including plaster)               3.30 kN/m2

Unit weight of block walls 15 cm*20cm*40cm (including plaster)               2.80 kN/m2

Unit weight of block walls 10 cm*20cm*40cm (including plaster)               2.20 kN/m2

Unit weight of structural steel                                                                         78.5 kN/m3

 

3.1.2 Minimum Super Imposed Dead Loads 

         

Stairs flooring                                                                                                 2.00 kN/m2

Horizontal concrete roof flooring                                                                   3.00 kN/m2

Offices and other areas flooring (100 mm floor finish)                                  2.00 kN/m2

Lightweight partitions per floor area                                                              1.00 kN/m2

False ceiling and services                                                                                0.50 kN/m2


 

3.2 Live Loads


3.2.1 Minimum Live Loads

Load Description

Uniformly

distributed load

kN/m2

- Domestic & residential areas

2.00

- Offices, meeting rooms, classrooms, laboratories dining rooms, cafes and restaurants.

3.00

- Stairs, Corridors, lounges & balconies

4.00

- Assembly areas with fixed seating

4.00

- Shopping and exhibition areas

4.00

- Mosques and Prayer Areas

5.00

- Car parking areas (not exceeding 2500 kg gross mass), aisle ways and ramps

2.50

-Roofs not accessible except for normal maintenance and repair.

0.60

- Mechanical (HVAC) Rooms

7.50

-Storage Areas

2.4 for each meter of storage height

 


3.3 Wind Loads

The buildings shall be designed for wind loads calculated in accordance with BS 6399, Part 2, using the standard method.

Basic wind speed (mean hourly wind speed)                                                    24 m/sec

Altitude factor                                                                                                    Sa = 1.0

Direction factor                                                                                                  Sd = 1.0

Seasonal factor                                                                                                   Ss = 1.0

Probability factor                                                                                               Sp = 1.0

 

3.4 Load Combinations

The structure shall be designed for load combination in accordance with BS 8110-1:1997 as follows:

 

3.4.1 Ultimate Limit State Load Combinations

1.4D

1.4D+1.6L

1.4D+1.4Wx

1.4D-1.4Wx

1.4D+1.4Wy

1.4D-1.4Wy

D+1.4Wx

D-1.4Wx

D+1.4Wy

D-1.4Wy

1.2D+1.2L+1.2Wx

1.2D+1.2L-1.2Wx

1.2D+1.2L+1.2Wy

1.2D+1.2L-1.2Wy


3.4.2 Serviceability Limit State Load Combinations

D

D+L

D+Wx

D-Wx

D+Wy

D-Wy

D+L+Wx

D+L-Wx

D+L+Wy

D+L-Wy

 

Where

D                        (SELF + WALLS + FLOOR COVER+CEILING)

L                         (Live)

SELF                      (Indicating self-weight of the structural elements)

WALLS                  (Indicating Internal Partitions Load)

COVER                 (Indicating Flooring Cover Load)

LIVE                      (Indicating Live Loads)

Wx                       (Indicating Wind Loads in X-Direction)

Wy                       (Indicating Wind Loads in Y-Direction)

 

4. Serviceability Limits States 

 

4.1 Deflection of Concrete

To avoid excessive deflections and damage to non-structural elements, the residual deflection after the initial camber shall be limited to the following values:

 

L/250         Total deflection.

L/500      Or 20 mm (whichever is lesser) for the part of deflection after the construction of brittle materials.

L/350      Or 20 mm (whichever is lesser) for the part of deflection after construction of non-brittle partitions or finishes.

 

For beams (L<= 10 m), it will generally be satisfactory to use the span/effective depth ratios given in BS8110-Part 1 table 3.9, clause 3.4.6.3 for reinforced concrete.

Where L is the span of the beam or slab or in the case of a cantilever its length.

Hussein Abdeldayem

أكثر من أربعة وعشرون (24) عامًا من الخبرة في مشاريع البناء والتشييد بما يخص تنفيذ واستلام بنود الاعمال المدنية والتشطيبات والتصميم الإنشائي وتقييم الحالة الإنشائية للمباني القائمة ووضع الحلول الإنشائية المناسبة لتحسين حالة المبنى وإعادة تأهيله، ونسعى إلى الاستثمار في اكتساب خبرات تنفيذ الأعمال المدنية والتشطيبات والتميز في مجال العمل والوصول لأكبر مكاسب في أقل وقت.